PCA For A Funeral Home

HEATING AND AIR CONDITIONING UNIT STUDY

Unit

Location

Area Served

Output BTUH Heating/Cooling

Age

Fuel

Condition
Furnace/ Condenser

Comments

1

over the ceiling of front layout room
foyer, main office, entry hall

60,000/18,000

1983

gas and elec.

good/fair

Gassy smell. Condenser is 1982. Furnace is 1989. Heat exchanger is in good condition.

2

same as above
front layout room

?/40,000

1985

gas and elec.

?/fair

Furnace was not readily accessible.

3

over the ceiling of embalm-ing room
rear sitting room, private office, hall, bathrooms

64,000/26,000

1983

gas and elec.

fair/fair

Main condensate drain and auxiliary are combined. Heat exchanger has much rust.

4

embalm-ing room wall
embalming room

11000/11800

1983

elec.

fair

Wall-mounted heat pump. Can draw in exhaust fumes from receiving garage.

5

main garage
layout rooms beside chapel

96,000/56,000

1983

gas and elec.

fair/fair

Some light rust on heat exchanger.

6

main garage
chapel

96,000/56,000

1983

gas and elec.

fair/fair

Heat exchanger is quite rusty.

7

over the ceiling of selection room
selection room

80,000/44,000

1989

gas and elec.

good/good

Some insulation is missing on the refrigerant line at the condenser.

8

main garage
hall and foyer

96,000/56,000

1983

gas and elec.

fair/fair

Heat exchanger is badly rusted.

9

receiving garage
receiving garage

22,500

1989

gas

good

Ceiling-mounted unit heater.

10

main garage
main garage

80,850

1983

gas

good

Ceiling-mounted unit heater.